    2 comments  ·  PI Interfaces » DNP3  ·  Flag idea as inappropriate…  ·  Admin →
    PrasadAvvaru supported this idea  · 
    An error occurred while saving the comment
    PrasadAvvaru commented  · 

    We also have similar issue while implementing PI for Transmission equipment. If the DNP3 interface creates a manually entered number (similar to interface id) for each RTU device as Device Number or RTU Number in the interface configuration and use this for Location 3 instead of RTU DNP address, it will solve the issue with PI Points. RTU is distinct with different IP and Port and Device DNP address, so interface can communicate with the devices, but the problem arises with PI Point configuration because of same DNP address across IO Groups (IP/Port).